Technical Specification | SUN2000-150K-MG0 |
Efficiency | |
Max. efficiency | European efficiency |
European efficiency | 98.4% |
Input | |
Max. Input Voltage 1 | 1,100 V |
Max. Current per MPPT | 48A |
Max. Current per Input | 23A |
Max. Short Circuit Current per MPPT | 66A |
Start Voltage | 200 V |
MPPT Operating Voltage Range 2 | 200 V ~ 1,000 V |
Number of MPP trackers | 7 |
Max. input number per MPP tracker | 3 |
Output | |
Nominal AC Active Power | 150,000 W |
Max. AC Apparent Power | 165,000 VA |
Max. AC Active Power (cosφ=1) | 165,000 W |
Nominal Output Voltage | 380 V/400 V/480Vac |
Rated AC Grid Frequency | 50 Hz / 60 Hz |
Nominal Output Current | 227.9 A @380 V, 216.5 A @400 V, 180.4A @480Vac |
Max. Output Current | 253.2 A @380 V, 240.5 A @400 V, 200.5A @480Vac |
Adjustable Power Factor Range | 0.8 leading… 0.8 lagging |
alternating current THDi | <1% |
Protection | |
Anti-islanding Protection | Yes |
AC Overcurrent Protection | Yes |
DC Reverse-polarity Protection | Yes |
PV-array String Fault Monitoring | Yes |
DC Surge Arrester | Type II |
AC Surge Arrester | Type II |
DC Insulation Resistance Detection | Yes |
Residual Current Monitoring Unit | Yes |
Smart String Level Disconnector | Yes |
Arc Fault Protection | Yes |
Terminal Temperature Detection | Yes |
PID Recovery | Yes |
PV Ground-Fault Protection | Yes |
Communication | |
Display | LED indicators; WLAN adaptor + FusionSolar APP |
RS485 | Yes
|
USB | Yes |
Smart Dongle-4G | Smart Dongle – 4G / WLAN (Optional) |
Monitoring BUS (MBUS) | Yes (isolation transformer required) |
General Data | |
Dimensions (W x H x D) | 1,000 x 710 x 395 mm |
Weight (with mounting plate) | 102 kg |
Operating Temperature Range | -25°C ~ 60°C |
Cooling Method | Smart Air Cooling |
Max. Operating Altitude | 4,000 m (13,123 ft.) |
Relative Humidity | 0 ~ 100% |
DC Connector | Amphenol HH4 |
AC Connector | Waterproof Connector + OT/DT Terminal |
Protection Degree | IP66 |
Topology | Transformerless |
Standard Compliance (more available upon request) | |
Certificate | EN 62109-1/-2, IEC 62109-1/-2, IEC 62116, IEC 61727, IEC 60068, IEC 61683 |
Grid Connection Standards | VDE-AR-N4105, EN 50549-1, EN 50549-2, RD 661, RD 1699, C10/11 |
- This datasheet only shows Preliminary Version, the information may change. Please contact with HW local supplier for the latest version.
* 1 The maximum input voltage is the upper limit of the DC voltage. Any higher input DC voltage would probably damage inverter.